KZ23.PK16 (MOV + GDT surge arrester) |
|||||||
|
Technical Data |
KZ23.PK16.U12DC |
KZ23.PK16.U24DC |
KZ23.PK16.U48DC |
KZ23.PK16.U60DC |
KZ23.PK16.U110DC |
||
|
Nominal Voltage |
UN |
12 V DC |
24 V DC |
48 V DC |
60 V DC |
110 V DC |
|
|
Max. continuous operating voltage |
UC |
14.4 V DC |
28.8 V DC |
57.6 V DC |
72 V DC |
132 V DC |
|
|
Nominal current |
In |
16A |
|||||
|
Combined impulse |
Uoc |
2 kV |
6 kV |
||||
|
Voltage Protection level at Uoc |
UP |
< 130 V (L+/L-) |
< 200 V (L+/L-) |
< 370 V (L+/L-) |
< 400 V (L+/L-) |
< 680 V (L+/L-) |
|
|
< 600 V (L/PE) |
< 600 V (L/PE) |
< 600 V (L/PE) |
< 600 V (L/PE) |
< 800 V (L/PE) |
|||
|
Response time |
tA |
< 25 ns (L+/L-) < 100 ns (L/PE) |
|||||
|
Recommended backup fuse |
16 A |
||||||
|
LPZ |
2-3 |
||||||
|
Protection type |
IP20 |
||||||
|
Operating temperature range |
|
-40°C to + 80°C |
|||||
|
Mounting on |
Din rail 35 mm |
||||||
0888 183 943